Bruksanvisning Drayton MiStat N Thermostat

Behöver du en bruksanvisning för din Drayton MiStat N Thermostat? Nedan kan du se och ladda ner PDF-bruksanvisningen gratis på svenska. Den här produkten har för närvarande 2 vanliga frågor, 0 kommentarer och har 0 röster. Om det här inte är bruksanvisningen du vill ha, vänligen kontakta oss.

Är produkten defekt och erbjuder bruksanvisningen ingen lösning? Gå till ett Repair Café för gratis reparationstjänster.

Bruksanvisning

Loading…

1.2m
INSTALLATION Guide
Step 3: Signal Strength
The MiStat Room thermostat is prebound to the
MiStat receiver in the factory so they just need
to be positioned in the best place for wireless
communication. To help with this there is a built in
Signal strength indicator, available in the Installer
settings menu on the MiStat thermostat, as shown.
It is recommended that the signal strength is Good
or Very Good to ensure ongoing communication is
maintained.
To enter signal strength menu (see step 5 for more detail))
Press + & - for approx. 5 secs, then scroll (+/-) to show
INST-S,
• press (
) to enter the installer menu,
• Press +/- until 11 WIRELESS is shown,
• press ( ) to enter,
• press +/- to show 13 SIG-LEVEL as shown,
• press ( ) to see the current signal strength.
Step 4: Mounting Options Step 5: Installer Settings
Once the best position has been identified, the MiStat N
should be fixed to the wall using the wall bracket as
shown.
Customize the MiStat according to application needs.
NB. MiStat can also be positioned using the table
stand included.
Care should be taken to mount the thermostat in a
position which is not subject to direct sunlight or
draughts. Preferably it should be mounted on an inside
wall about 1.2m (4ft) above the floor in a position where
it can respond to room temperature but away from the
direct influence of radiators or other appliances giving
off heat.
MiStat
MiStat
Step 1: Mounting the Wall-plate Step 2: Wiring
! IMPORTANT:
Installation must only be carried out by a
qualified electrician or heating engineer.
Make sure mains input has a 3 amp fuse.
! CAUTION! Before installation, make sure the
mains supply is switched off!
Option 2: Using an existing wall-plate
Loosen the securing screws on the old receiver
and unplug it. Check that there’s 20mm
clearance to the right of the wall-plate and 25mm
above it. Check the wiring diagram for your
product model to compare terminals and, if
necessary, change the wiring of the wall-plate to
suit. Now plug the MiStat R unit into the
wall-plate and tighten the securing screws.
Check the 3A fuse, and switch on the mains.
Option 1: Fitting a new wall-plate
The ideal location is close to the boiler or central
heating system. For the best performance install
in an open space, at least 30cm distance from any
metal objects including wall boxes and the boiler
housing. It is recommended that the MiStat R is
mounted on the wall nearest the final location of
the MiStat N room unit and not less than 30cm
from the boiler side panel.
Loosen the securing screws, remove the wallplate
and, if surface wiring is to be used, snap out
the cable entry strip on the bottom edge of the
wallplate with a pair of pliers. Fix the wallplate,
terminals at the top, either direct onto the flat
wall using wall plugs and no 6 x1” wood screws
or on a plastic flush mounting single conduit box
using M3.5 x 14 screws. Check that there’s 20mm
clearance to the right of the wall-plate and 25mm
above it. Complete the wiring to the MiStat R
wallplate in accordance with the wiring diagram
in step 2, to comply with current IEE regulations.
Place the MiStat R onto the wallplate and tighten
the securing screws.
Check the 3A fuse, and switch on the mains.
Warning: Installing the MiStat R too close to the
metal side panel or mains cables may interfere
with the radio signal.
Applications
The electronic room thermostat MiStat N can be used
for temperature control together with:
Boilers
Oil and gas warm water heating
Actuators of floor heating systems or radiators
Circulating pumps
Heat pumps
A MiSat R receiver is required for operation.
Note: To ensure a properly working heating
system, the menu items in the Installer settings
have to be set according to the needs of the
heating system, see step 5.
Note: To ensure a properly working heating system,
the menu items in Installer settings have to be set
according to the needs of the heating system.
There can be gaps in the ID numbering.
! DO NOT
use a surface
mounting box
This product is double insulated and
does not require an earth connection.
The MiStat R should be wired to the
boiler or central heating wiring using the
correct type of cable or flex. The MiStat
R should be wired to replace hard wired
room or programmable thermostats,
as shown on the system or boiler wiring
diagrams.
Always check other manufacturers
instructions for compatibility.
N L 1 2 3
230V AC 50Hz
Fused 3A
Common
heating
satisfied
or call for
cooling
Call for
heat
Volt free contacts
Combi boiler basic wiring layout
Zone control basic wiring layout
Note: If not bound, the bind screen will be visible.
For commissioning see Step 6
Note: Only needed if not already bound, ie if
replacing either the MiStat thermostat or the
MiStat receiver.
To exit Installer Settings
Press +/- until ‘DONE’ is shown, then press ‘Select’ or
press + & – keys for approx. 5 seconds to exit. If there
is no key pressed for 2 Minutes, the system will exit the
menu, any changes will be saved.
1. Turn on power for the receiver. The red lamp will
come on. (if green lamp is visible, the device is
already bound, no further action needed here)
(If a separate programmer/Timer is fitted, ensure
that it is switched on)
2. Push the button for >5 Seconds and the LED will
flash red yellow green --- -red yellow - green…
3. Enter binding mode on the corresponding
MiStat room unit, see Step 5: Installer settings ,
item 11
Important: It is essential, that the binding is
carried out between the corresponding room
unit and the receiver
4. If binding is successful, the signal strength will
be indicated on both the MiStat room unit and
the MiStat receiver as follows. If unsuccessful,
FAILED will be displayed. If POOR SIGNAL
is displayed, look for a better location. If NO
SIGNAL is displayed, try connecting again with
the room unit in a different position.
MiStat Room Unit
MiStat Receiver
Immediately after binding, these signals will indicate
the signal quality for 1 minute.
three green flashes = Very good signal
double amber flashes = Good signal
single red flashes = Poor signal
steady red = No signal
To check the wireless connection
A green lamp on the receiver will indicate a good RF
connection.
To enter Installer Settings
Press + & – keys for approx. 5 Seconds to enter the
settings menu as shown.
Note: If not bound, the bind screen will be visible.
For commisioning see Step 6
Technical Data
Step 6: Commissioning
MiStat N110R & MiStat R111M
Supply voltage MiStat N: 2 x AA 1,5V alkaline
batteries
MiStat R: 230V
Switch rating MiStat R: 2(1)A 230V a.c.
Ambient
temperature
Operating: 0°C to 45°C;
Storage: –20°C to 55°C;
Battery life MiStat N: 2 years (typically)
Temperature
range
5°C to 30°C
Temperature
resolution
0.5 °C, display and setting
Control accuracy <0.6°C at 4°/hour
Wiring Mistat R: Fixed wiring only, to comply
with current IEE regulations (BS7671)
MiStat N: No wiring required
Mounting MiStat R: Industry standard wallplate
MiStat N: Wall bracket or table stand
Radio frequency 868.3 (Bi-directional communication)
Radio signal range 30m typically. The range may be
affected by the composition / density
and number of walls between the
MiStatN and MiStatR
Pollution degree 2
Software class A
Rated impulse
voltage
MiStat R: 2.5kV
Ball pressure test
temperature
MiStat R: 75°C
Relevant EC
Directives:
2006/95/EC Low Voltage Directive
2004/108/EC Electromagnetic
Compatibility Directive
1995/5/EC R&TTE Directive
2006/66/EC Battery Directive
2011/65/EU RoHS Directive
Applied
Standards:
EN60730-1; EN60730-2-9
ETSI EN 300 220-3; ETSI EN 301 489-3
eg. eg.
eg. eg.
User Code:
N L 1 2 3
L
MiStat R
MiStat R
Switched live
from wiring
centre
Motorised valve
N
To boiler
and/or
pump
Radio signals
to MiStat R - no wiring
230V AC
fused 3A
N L 1 2 3
L -
N -
Radio signals
to MiStat R - no wiring
Sw
i
tched
230V AC
fused 3A,
Internal
boiler
electronics
External
controls
connections
N L 1 2 3
L
MiStat R
MiStat R
Switched live
from wiring
centre
Motorised valve
N
To boiler
and/or
pump
Radio signals
to MiStat R - no wiring
230V AC
fused 3A
N L 1 2 3
L -
N -
Radio signals
to MiStat R - no wiring
Sw
i
tched
230V AC
fused 3A,
Internal
boiler
electronics
External
controls
connections
If POOR is displayed, look for a better location.
If NO SIGNAL is displayed, try connecting again with
the room unit in a different position.
Caution!
The radio receiver may be installed only by a competent
electrician in compliance with the circuit diagram
enclosed in the top housing cover or in compliance
with these instructions. The current safety regulations
must be observed.
In order to achieve protection class II, adequate
installation measures must be taken.
This radio receiver, which can be installed separately,
is designed exclusively for temperature control in dry
and closed rooms and standard environments. This
electronic device was created according EN60730-1, it
operates according working principle 1C.
It has to be placed in a location where it will be able to
control the room temperature.
6444 Invensys MiStat N 06490191001 IssE.indd 2 27/09/2013 09:26
Ladda ner bruksanvisning i Engelska (PDF, 3 MB)
(Tänk på miljön och skriv endast ut denna bruksanvisning om det verkligen är nödvändigt)

Loading…

Betyg

Berätta vad du tycker om Drayton MiStat N Thermostat genom att betygsätta den. Vill du dela med dig av dina åsikter om denna produkt eller ställa en fråga? Lämna en kommentar nederst på sidan.
Är du nöjd med Drayton MiStat N Thermostat?
Ja Nej
Bli den första personen som betygsätter denna produkt
0 röster

Delta i konversationen om denna produkt

Här kan du dela vad du tycker om Drayton MiStat N Thermostat. Om du har en fråga, läs först noggrant igenom manualen. Att begära en manual kan göras genom att använda vårt kontaktformulär.

Mer om denna bruksanvisning

Vi förstår att det är trevligt att ha en pappersbruksanvisning för din Drayton MiStat N Thermostat. Du kan alltid ladda ner bruksanvisningen från vår hemsida och skriva ut den själv. Om du vill ha en originalbruksanvisning rekommenderar vi att du kontaktar Drayton. De kanske kan tillhandahålla en originalbruksanvisning. Letar du efter bruksanvisningen för din Drayton MiStat N Thermostat på ett annat språk? Välj ditt föredragna språk på vår hemsida och sök efter modellnumret för att se om vi har det tillgängligt.

Specifikationer

Märke Drayton
Modell MiStat N
Kategori Thermostater
Filtyp PDF
Filstorlek 3 MB

Alla bruksanvisningar för Drayton Thermostater
Fler bruksanvisningar för Thermostater

Vanliga frågor om Drayton MiStat N Thermostat

Vårt supportteam söker efter användbar produktinformation och svar på vanliga frågor. Om du hittar en felaktighet bland våra vanliga frågor uppskattar vi om du meddelar oss detta via vårt kontaktformulär.

Vad är en termostats döda zon? Verifierad

Många moderna termostater har en död zon. Om temperaturen avviker från mindre än 4 ° C från den inställda temperaturen värms eller svalnar systemet inte. Denna så kallade termostats döda zon förhindrar att systemet slås på och av för ofta, vilket sparar energi.

Detta hjälpte (1754) Läs mer

Vad är det bästa stället att montera en termostat på? Verifierad

Det bästa stället för en termostat är cirka 1,5 meter över marken. Placera aldrig termostaten i en radiator eller annan värmeavgivande utrustning eller i direkt solljus. Välj ett rum som används ofta. I de flesta fall är detta vardagsrummet.

Detta hjälpte (1124) Läs mer
Bruksanvisning Drayton MiStat N Thermostat

Relaterade produkter

Relaterade kategorier

×
Download